FSP UPS ONLINE CHAMP 2K TOWER 2000VA 1800W 230V IECx4CHAMP PPF16A1905
FSP UPS ONLINE CHAMP 2K TOWER 2000VA 1800W 230V...

FSP UPS ONLINE CHAMP 2K TOWER 2000VA 1800W 230V IECx4CHAMP PPF16A1905

FSP
FSPCHAMP2KTOWER
4711140487601
PPF16A1905
€356.24
Tax included

Disponibile

 

CHAMP ups is specifically designed for operation in poor power area. It provides high power density with long backup time in compact size. User also can adjust charging current from 1A to 6A according to different application


Feature

  • True double conversion
  • Microprocessor control optimizes reliability
  • Input power factor correction
  • Output power factor 0.9
  • Wide input voltage (120V-300V)
  • Converter mode available
  • ECO mode for energy saving
  • Generator compatible
  • Smart SNMP works well with either USB or RS-232 together
  • Comprehensive display allows easy monitoring and access of UPS status



Uninterruptible Power System Champ 1k/2k/3k | FSP TECHNOLOGY INC. (fsp-group.com)

**SPECIFICATIONS:

** MODEL
Champ 1K Champ 2K Champ 3K
** CAPACITY
1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W
** INPUT
Voltage Range:
- Low Line Transfer
90Vac/80Vac/70Vac/60Vac± 5% or 180Vac/160Vac/140Vac/120Vac± 5% (Ambient Temp.<350C) ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
- Low Line Comeback
100Vac/90Vac/80Vac/70Vac or 195Vac/175Vac/155Vac/135Vac ± 5 % (Ambient Temp.<350C) ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
- High Line Transfer
145 Vac ± 5 % or 300 Vac ± 5 %
- High Line Comeback
140 Vac ± 5 % or 290 Vac ± 5 %
- Frequency Range
40Hz ~ 70 Hz Phase Single phase with ground Power Factor ≧ 0.99 @ nominal voltage (input voltage)
** OUTPUT
- Output voltage
110/115/120/127Vac or 208/220/230/240Vac
- AC Voltage Regulation
± 1% (Batt. Mode)
- Frequency Range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
- Frequency Range (Batt. Mode)
50 Hz ± 0.5% or 60Hz ± 0.5%
** Overload
- Ambient Temp.<350C
105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal
110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal
>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
- Current Crest Ratio
3:1
- Harmonic Distortion
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
- Transfer Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
** EFFICIENCY
- AC Mode
88% 89% 90%
- Battery Mode
83% 87% 88%
** BATTERY
- Standard Model Battery
Type 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah
Numbers 2 4 6
Recharge Time 4 hours recover to 90% capacity (Typical)
Charging Current 1.0 A (max.)
Charging Voltage 27.4 Vdc ± 1% 54.7 Vdc ± 1% 82.1 Vdc ± 1%
- Long-run Model*
Battery Numbers 2 3 4 6 6 8
Charging Current 1.0A/2.0A/4.0A/6.0 A
Charging Voltage 27.4 Vdc ± 1% 41.0Vdc ± 1% 54.7 Vdc ± 1% 82.1Vdc ± 1% 82.1 Vdc ± 1% 109.4Vdc ± 1%
** PHYSICAL
- Standard Model
Dimension, D X W X H 282 X 145 X 220 (mm) 397 X 145 X 220 (mm) 421 X 190 X 318 (mm)
Net Weight (kgs) 9.8 17.0 27.6
** Long-run Model*
Dimension, D X W X H 282 x 145 x 220 (mm) 397x 145 x 220(mm)
Net Weight (kgs) 4.1 4.1 6.8 6.8 7.4 7.4
** ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter
** MANAGEMENT
Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMP Power management from SNMP manager and web browser

Disponibile

No reviews
Product added to wishlist
Product added to compare.